4.5.3.7 Basic function
–
Dimming
Single-button function
Two- button function
Important:
Basic functions for the single-button function are available for selection if the
function of buttons 1 or 2 is set to "external function"!
The following figure shows the available settings (here with the two-button function):
Figure 49: Settings
–
Dimming
The following table shows the available settings:
ETS-Text
Dynamic range
[Default value]
Comment
Button assignment 1/2
▪
brighter/darker
▪
darker/brighter
Only with two-button function!
Setting the button assignment for
the direction (brighter/darker).
Table 94: Settings
–
Dimming
With the single-button function "Dimming", two communication objects appear for this button.
Firstly, the function for a short button action, the "Dimming On/Off" switch object, and secondly the
function for a long button action, the dimming object "Dimming relative".
The two-
button function “dimming” can be set either as brighter/darker or as darker/brighter. The
relationships are shown in the following table:
Table 95: Functionality
–
Two-button Dimming
With the single-
button function “dimming”, the direction (brighter/darker) is reversed
depending on
the communication object "Status for toggle".
The dimming function is a start-stop dimming function, i.e. as soon as the dimming function
becomes active, a brighter or darker command is assigned to the input until it is released. After the
command is released, a stop telegram is sent which ends the dimming process.
Function brighter/darker
Function darker/brighter
Input
Button 1
Button 2
Button 1
Button 2
Dimming function
brighter
darker
darker
brighter
Switching function
ON
OFF
OFF
ON