Status object
The following status objects are available for the ventilation control (are permanently visible):
•
1 Byte output
If the state object is parameterized as 1 Byte, the object sends the current level as value,
e.g. value 1 for level 1, value 2 for level 2…
With the setting “step
-
switch as byte”, the current control value is sent.
•
1 Bit
–
Ventilation active
In this case, the value 1 is sent when the ventilation is active and the value 0 when the
ventilation is inactive.
The following table shows the associated communication objects:
Number Name/Function
Length Usage
47
Ventilation control
–
1Byte status ventilation level
1 Byte Output of the current status, which level is
active
53
Ventilation control
–
Status ventilation active
1 Bit
Output of the status whether active or not
Table 76: Communication object
–
Status of ventilation control
4.4.5.2 Step Switch
–
binary coded
The functionality of the binary coded step switch is identical to that of the normal step switch as
described under "
". Only the output stage is already transmitted
in binary code. Object 43 is bit 0, object 44 is bit 1 and object 44 is bit 2.
The following table shows the binary-coded switching of the output level:
Normal step-switch
Binary value
Step-switch binary coded
Level 0
000
Objects 43, 44, 45 = 0
Level 1
001
Object 43 = 1, Objects 44& 45 = 0
Level 2
010
Object 44 = 1, Objects 43 & 45 = 0
Level 3
011
Objects 43 & 44 = 1, Object 45 = 0
Level 4
100
Object 45 = 1, Objects 43 & 44 = 0
Table 77: Settings
–
Step-switch binary coded
The following table shows the communication objects for the step switch binary coded:
Number Name/Function
Length Usage
43
Ventilation control
–
Bit 0
1 Bit
Setting the bit 0
44
Ventilation control
–
Bit 1
1 Bit
Setting the bit 1
45
Ventilation control
–
Bit 2
1 Bit
Setting the bit 2
Table 78: Communication objects
–
Step switch binary coded