2.5 Commissioning
After wiring the unit, the physical address is assigned, and the application is programmed:
(1)
Connect the programming interface with the bus, e.g. with MDT USB Interface.
(2)
Switch-on bus voltage.
(3)
Activate programming mode by actuating the sensor areas 5 and 6 on the unit
simultaneously (as soon as the unit is in programming mode, this is shown in the display.
Status LEDs on the right and left of the unit light up red alternately).
(4)
Loading of the physical address out of the ETS-Software by using the interface (The display
changes to normal mode as soon as this is successfully completed).
(5)
Loads the application with the desired parameterization (programming progress is shown in
the display). Switches to normal operation as soon as this has been successfully completed.
(6)
If the device is enabled, you can test the requested functions (also possible by using the
ETS-Software).