Technical Manual
Glass Room Temperature Controller Smart SCN-RTRGx.02
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
•
Germany
Phone: +49-2263-
880 • [email protected] • www.mdt.de
97
97
4.5.4.2 Buttons 3/4
–
Temperature shift as extension unit
If the internal controller is set as "extension unit", the type of temperature shift is set in the menu
for buttons 3/4.
The following settings are available here (here for the shift over 2byte):
Figure 56: Settings
–
Buttons 3/4: Temperature shift as extension unit
The following table shows the available settings:
ETS-Text
Dynamic range
[Default value]
Comment
Temperature shift
▪
1Bit
▪
1Byte
▪
2Byte
▪
2Byte temperature setting
Selection of the type of temperature
shift
Step width of setpoint shift
0,1 … 1 K
[0,5 K]
Setting of the step size between two
send commands.
Not displayed for shift via 1 bit
Lower limit
-
10 … 10 K
[-3 K]
Setting of the lower limit value for
the setpoint shift.
Only for shift via 1byte/2byte
Upper limit
-
10 … 10 K
[3 K]
Setting of the upper limit value for
the setpoint shift.
Only for shift via 1byte/2byte
Lower limit
0 … 45 °C
[17 °C]
Setting of the lower limit value for
the setpoint shift.
Only for shift via 2byte
temperature setting.
Upper limit
0 … 45 °C
[25 °C]
Setting of the upper limit value for
the setpoint shift.
Only for shift via 2byte
temperature setting.