Technical Manual
Glass Room Temperature Controller Smart SCN-RTRGx.02
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
•
Germany
Phone: +49-2263-
880 • [email protected] • www.mdt.de
80
80
The following table shows the available settings:
ETS-Text
Dynamic range
[Default value]
Comment
Mode selection
▪
Comfort / Standby / Night /
Frost (Heat) protection)
▪
Comfort / Standby / Night
▪
Comfort / Standby / Frost
(Heat) protection
▪
Comfort / Night / Frost (Heat)
protection
▪
Comfort / Standby
▪
Comfort / Night
▪
Comfort / Frost (Heat)
protection
▪
Comfort
▪
Standby
▪
Eco/ Night
▪
Frost (Heat) protection
Setting between which operating
modes can be switched.
No switchover when other
operating mode
If checked, then note text in blue box
Only visible if 2 or 3 operating
modes are selected.
Activation locks a switchover if
another operating mode than the
selected one is active.
Table 84: Settings
–
Mode selection (internal connection)
No switchover when other operating mode:
If the function is activated by setting the check mark, the button can only be used to switch
between the set operating modes if one of these operating modes is active. If, for example,
"Operating mode switchover - Comfort/Night" was set and "Frost protection mode" was triggered
by another event, e.g. by opening a window, the button cannot be used to switch any further. Only
when the operating mode is set to "Comfort" or "Night" again can you switch over with the button.
Note:
According to the setting in the "Mode selection" parameter, a message appears in a blue box
indicating the operating mode that cannot be switched over.
Example:
Mode section: “Comfort/Standby/Night”
No switchover when other operating mode
:
marked
Operation as extension unit:
Mode selection is sent to an external controller by object 15. The status is received by object 20.
The following table shows the available communication objects:
Number Name/Function
Length Usage
15
Mode selection
–
Send mode
1 Byte Sending the operating mode
20
DPT_HVAC Status
–
Receive controller status
1 Byte Receiving the controller status
Table 85: Communication objects
–
Mode selection (extension unit)
For a description of "Display" and "Lock object", see chapter