Technical Manual
Glass Room Temperature Controller Smart SCN-RTRGx.02
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
•
Germany
Phone: +49-2263-
880 • [email protected] • www.mdt.de
87
87
4.5.3.6 Basic function
–
Switch/Send values short/long (with 2 objects)
Single-button function
Important:
Basic functions for the single-button function are available for selection if the
function of buttons 1 or 2 is set to "external function"!
The following figure shows the available settings:
Figure 48: Settings
–
Switch/Send values short/long (with 2 objects)
The following table shows the available settings:
ETS-Text
Dynamic range
[Default value]
Comment
Action
for
short/long
keypress
–
Object 1/2
▪
OFF
▪
ON
▪
toggle
▪
send value
▪
not active
Setting the action for the
short/long button.
Datapoint type
▪
1Byte DPT 5.005 Decimal
factor (0…255)
▪
1Byte DPT 5.001 Percent
value (0…100%)
▪
1Byte DPT 17.001 Scene
number
Setting of the datapoint type for
the value to be sent.
Setting only available if "Action
for short/long keypress" is set
to "send value".
Table 92: Settings
–
Switch/Send values short/long (with 2 objects)
With the basic function "
Switch/Send values short/long (with 2 objects)
", 2 different values can
be sent for a short and long keypress. The objects can be different. This makes it possible to send
different types of datapoints.
With "
value: ON
" or "
value: OFF
", the same fixed value is always sent.
When “
toggle
” is set, On/Off is sent alternately.
With "
send value
", the set value is always sent, either as a percentage value, decimal value, or
scene. The adjustable values are: 0 - 100% (percent value), 0 - 255 (value) or 1 - 64 (scene).
Important
: The status display always applies to the "short button"/object 1!