363-205-401
Power Up: DLP-522
Issue 7, March 1997
Page 5 of 8
15.
NOTE:
Connectors are "keyed" and must be properly oriented to be connected.
Connect patch cord [Figure 2] to BAT (
−
) connector of battery 5.
Figure 2 – Chloride Battery String Connections and Position in 80A Cabinet
16. As shown in Figure 2, place batteries 5 through 8 (with cable assemblies) in
battery compartment in position for battery string 1 or 2.
17.
!
DANGER:
When connecting batteries together, be careful not to connect together
the positive and negative terminals of the same battery.
Connect batteries together by plugging BAT (
−
) connector from one battery
into BAT (+) connector from next battery [Figure 2].
BATTERY
BATTERY
BATTERY
PATCH
CABLE
STRING
BARRIER
4
6
7
8
1
5
CABLE
5
4
6
7
1
8
STRING 1
3
2
ASSEMBLY
STRING 2
3
2