Power Up: DLP-530
363-205-401
Page 2 of 6
Issue 7, March 1997
3.
NOTE:
FAIL indicator on PCU may light momentarily when inserted into RT
optics power shelf.
Does FAIL indicator on PCU go off and remain off?
If YES, then proceed to Step 8.
If NO, then continue with Step 4.
4.
Replace PCU.
5.
NOTE:
FAIL indicator on PCU may light momentarily when inserted into RT.
Does FAIL indicator on PCU go off and remain off?
If YES, then proceed to Step 8.
If NO, then continue with Step 6.
6.
Replace PCU with PCU removed previously.
7.
Use SD-7C150-01 to check RT optics power shelf wiring. Repeat procedure
from Step 3 after locating and correcting trouble.
8.
Is MJ indicator on A/FCU lighted?
If YES, then proceed to Step 9.
If NO, then continue with Step 10.