Advance Printing
Power Up: DLP-523
363-205-401
Page 6 of 6
Issue 7, March 1997
23. Disconnect test equipment. Reconnect any battery strings disconnected for
voltage measurement. Turn AC breaker on. Close and lock battery compart-
ment door.
Comment:
Battery current can be measured on the AUG4 BIU by mea-
suring millivolts DC between + and - for battery string 1 or 2.
One millivolt DC corresponds to 1 AMP DC. A positive read-
ing (+ to - with the common meter lead in -) indicates the bat-
teries are being charged.
24. Between one and three hours after the rectifiers are installed, measure the
voltage of each battery in the string and record on form 1285 supplied with the
batteries. Meter should indicate between 4.44 V DC and 4.64 V DC for each
battery. Any battery outside this limit should be measured again within one
week. If it is still outside the limit, replace battery.
STOP. YOU HAVE COMPLETED THIS PROCEDURE.