363-205-401
RT Turn Up: NTP-003
Issue 7, March 1997
Page 3 of 8
DO ITEMS BELOW IN ORDER LISTED
FOR DETAILS, GO TO
NOTE:
The term "facility shelf" is used throughout this procedure to
refer to the middle shelf in the Series 5 RT. The remaining
shelves will be referenced according to digroup name (for
example, AB shelf contains digroups A and B). White system
refers to the two upper shelves of the Series 5 RT plus the
right half of the facility shelf and blue system refers to the
two lower shelves of the Series 5 RT plus the left half of the
facility shelf.
Install 3-type protectors in protector panel for shelf group(s) being
equipped.
4.
Verify, per work order, that the correct complement of circuit
packs is available.
5.
If the blue (lower) system is being equipped continue with Step 6.
Otherwise, to equip the white system, proceed to Step 9.
6.
If required [the LFU is required if AUA62( ) line powering LIUs are
used], install and check fuses in LFU (line fuse unit) in facility
shelf.
7.
Install and test PCU (power converter unit) in facility shelf.
8.
NOTE:
The 4A fan does not require the FCU but should be tested by
pressing the test button (at least 3 times) and verifying the
fan runs fast, slow, and stops.
Install FCU (fan control unit) [if 2( ) FAN UNIT is installed].
9.
Install and check fuses in CFU (channel fuse unit).