![LST BC016 Series Скачать руководство пользователя страница 23](http://html1.mh-extra.com/html/lst/bc016-series/bc016-series_user-manual_1944502023.webp)
Connection of detectors Labor Strauss
Chapter 2 • Conventional technology
23
2.4.2
Automatic detectors Series FC650
The following fire detectors can be connected to a conventional detector interface of the fire detection
control panel:
Description
Type
max. number per detector zone
Optical Smoke Detector
FC650/O
32
Thermal Rate-of-rise Detector FC650/TDIFF/57
32
A1R – 57°C
Thermal Max Detector
32
EN 54-5 class
FC650/TMAX/78
1)
BS
1)
– 78°C
1)
Class BS applies from firmware version 1.18 on. Thermal detectors with an earlier firmware version comply
with class B and were delivered as type FC650/T/78. The firmware version can be found on the label on the
bottom of the detector.
In the case of the detector FC650/O, the degree of contamination can be read out by means of the Pro-
gramming Unit FI700/PU (or the FI750/PU with an appropriate adapter).
In the case of the heat detectors FC650/TDIFF/57 and FC650/TMAX/78, the class according to
EN 54-5 can be changed
–
see Chapter 3.3.2.7: „Expert mode“ on page 102.
At the time of shipment, the class according to EN 54-5 is marked by means of a label on the bottom
of the detector. If you should change the class, the label has to be updated manually.
With all Series FC650 detectors, the Programming Unit FI700/PU (or the FI750/PU with an appropriate
adapter) can be used to determine the function of the status LED in the normal condition (dark/flashing).
The Series FC650 detectors can be used with the Detector Bases FC600/BR, FC600/BRD and
FC600/BREL.
2.4.2.1 Arrangement of wires in Detector Base FC600/BR, FC600/BRD, FC600/BREL
Strip the insulation just as short as the terminal requires for connection. The alarm resistor R = 1kOhm
between terminals „R+“ and „+“ is already connected. Keep in mind to connect the end-of-line element
(resistor or capacitor) at the terminals „R+“ and „OUT“ of the last element.
The removal of a detector from the Detector Base FC600/BR will open the conventional zone and a
fault (broken wire) will be displayed at the panel.
The use of the Detector Base FC600/BRD, which has a built-in diode, prevents the conventional zone from
being opened when a detector is removed from its base. As a consequence, a capacitor has to be defined as
end-of-line element – for further instructions please consult the corresponding manual of the fire detection
panel.
If a Remote Indicator PA58-3 is used, a 1kOhm series resistor has to be inserted between terminal
„RA“ of the detector base and the Remote Indicator PA58-3. Since detector production code 2011/48,
the series resistor can be omitted.
Connection-LST.odt / 2009 / AN9161298
200/23
23