Connection of detectors Labor Strauss
Chapter 3 • ADM technology
167
3.11.3
Combi module with four (4) supervised inputs and four (4) relay outputs
3.11.3.1 Address setting
Detailed information can be found on page 95 in Chapter 3.3: „Address programming of loop ele-
ments“. Each input or output occupies a separate address.
The preset address (X) refers to the first input. The other inputs and the outputs have consecutive
addresses.
Input 1 = X; Input 2 = X+1; Input 3 = X+2; Input 4 = X+3
Output 1 = X+4; Output 2 = X+5; Output 3 = X+6; Output 4 = X+7
3.11.3.2 Function of the LEDs
A summary LED is available both for the inputs and for the outputs.
For the inputs:
In the idle condition of all inputs, the LED will blink in green.
The LED will blink in red if an input is active.
In case of a fault of an input, the LED will be continuously illuminated in yellow.
For the outputs:
The LED will be continuously illuminated in green when at least one output is active.
3.11.3.3 Connection of Combi Module FI700/M4IN4REL
Connection-LST.odt / 2009 / AN9161298
200/167