26
Chapter 2 • Conventional technology
Connection of detectors Labor Strauss
2.4.2.6 Connection of detectors with Relay Base FC600/BREL
The contact rating of the relay is 1A at 30VDC.
A 1kOhm series resistor has to be inserted between terminal „RA“ of the detector base and the
Remote Indicator PA58-3. Since detector production code 2011/48, the series resistor can be omitted.
Connection-LST.odt / 2009 / AN9161298
200/26