Connection of detectors Labor Strauss
Chapter 3 • ADM technology
143
3.8.21
Smoke Aspiration System Titanus TOP SENS – TT-1 with 2 detector modules
For the operation of the smoke aspiration system on Control Panels Series BC216 and BC600, a firm-
ware from calendar week 12 / 2013 or later is to be used, and the reset output of the conventional zone
module is to be set to Pulsed signal. If an older firmware is used, the smoke aspiration system will be
deactivated if one of the two modules is disabled!
If the conventional zone module is powered by an external power supply, the country-specific regula-
tions concerning emergency power supply have to be observed.
Connection-LST.odt / 2009 / AN9161298