Connection of detectors Labor Strauss
Chapter 2 • Conventional technology
25
2.4.2.4 Connection of detectors with Remote Indicator PA58-3 and Address Module NG58-1
Up to three remote indicators can be connected to the remote output of the detector. For this application
the „TAB“ of the remote indicator has to be broken out. When only one remote indicator is connected to
the detector, the „TAB“ must not be broken out. The alarm resistor between terminals „R+“ and „+“ is
already integrated.
A 1kOhm series resistor has to be inserted between terminal „RA“ of the detector base and the
Remote Indicator PA58-3. Since detector production code 2011/48, the series resistor can be omitted.
2.4.2.5 Connection of detectors with Remote Indicator PA58-3 and Address Module NG58-1
A 1kOhm series resistor has to be inserted between terminal „RA“ of the detector base and the
Remote Indicator PA58-3. Since detector production code 2011/48, the series resistor can be omitted.
If an address module is connected to more than one detector, the address module is activated in the
alarm condition of
one
of these detectors and indicates the preset address.
Connection-LST.odt / 2009 / AN9161298
200/25