Chapter 3 • ADM technology
Connection of detectors Labor Strauss
3.5.2.2 Connection of detector bases FI700/B, FI700/BD, FI700/BREL with PA58-3
Multiple indicators can
not
be connected to detectors Series FI700.
If the remote indicators are connected to Fire Detection Control Panels Series
BC216,
a maximum of
8 remote indicators can be simultaneously activated per loop, because the number of detector/module
LEDs that can be activated is limited.
If the remote indicator is used on the
BC600,
the parallel output of the detector can be freely paramet-
erised according to the requirements. This is done with the RI setting „individual“. In this case the
limitation of 8 detector/module LEDs that can be activated is cancelled for this output. Therefore it is
all the more important to check the maximum number of sounders by means of the loop calculator
spreadsheet FireSysCALC_xxx.ods (available in the download area of the LST website – registration
required).
Connection-LST.odt / 2009 / AN9161298