Connection of detectors Labor Strauss
Chapter 3 • ADM technology
141
3.8.19
Smoke Aspiration System Titanus PRO·SENS – TP1/A with 2 detector modules
On pin connector JU2/3 (main printed circuit board of the smoke aspiration system), the jumper has to
be set to position 1-2, which means that the fault relay is set to operate as NORMALLY OPEN contact.
For the operation of the smoke aspiration system on Control Panels Series BC216 and BC600, a firm-
ware from calendar week 12 / 2013 or later is to be used. If an older firmware is used, the smoke
aspiration system will be deactivated if one of the two modules is disabled!
If the conventional zone module is powered by an external power supply, the country-specific regula-
tions concerning emergency power supply have to be observed.
Connection-LST.odt / 2009 / AN9161298