Chapter 4 • Analogue values - Condition of detectors/modules
Connection of detectors Labor Strauss
4.2
Standard detectors
4.2.1
Optical smoke detectors
The table below applies to the detectors FI700/O and FI750/O.
Value
Meaning
0
1-191
Detector OK
>191
Alarm
Detector defective, removed or short circuit on the loop
4.2.2
Thermal detector
The table below applies to the detectors FI700/T and FI750/T.
Value
Meaning
0
1-191
Detector OK
>191
Alarm
Detector defective, removed or short circuit on the loop
4.2.3
Optical-thermal detectors
The table below applies to the detectors FI700/OT and FI750/OT.
Value
Meaning
0
1-191
Detector OK
>191
Alarm
Detector defective, removed or short circuit on the loop
4.2.4
Manual call points
The table below applies to the Manual Call Points (Series MCP / HFM / HME).
Value
Meaning
0
32
Detector OK
>191
Alarm
Detector defective, removed or short circuit on the loop
Connection-LST.odt / 2009 / AN9161298