Connection of detectors Labor Strauss
2.13.14 Sounder-Strobe CWSS-xx-xx
DIP switch 6 is used for setting the sound level: 0 = medium; 1 = high.
By means of the DIP switches 1 through 5 the tones can be set. Tone 2 results from the switch position.
DIP switch
1
2
3
4
5
Tone 1
Tone 2
1
0
1
0
1
1200-500Hz DIN tone
DIN, PFEER
1
1
1
0
1
500-1200Hz Slow whoop tone
NEN2575
1
1
0
0
1
800Hz – BS tone
BS5839 Pt1
Connection-LST.odt / 2009 / AN9161298