Connection of detectors Labor Strauss
Chapter 3 • ADM technology
115
3.6.2.2 Flame Detectors – Series 16000
Thanks to the ignition protection class „flameproof enclosure“, the flame detector can be used without
the Safety Barrier ES58-2 or Zener Barrier Z978.
Type
EN 54-10 Class 1
SW6
SW7
Response time
16511
IR2
0
0
8s
16519
IR3
1
0
4s
16521
UV/IR2
0
1
2s
1
1
1s
By means of the DIP switches, the detector can be adjusted to the various operating conditions. The
switches 6 and 7 allow you to change the response time.
The installation in the hazardous area has to comply with EN 60079 because the energy in the line is
not limited by barriers.
Connection-LST.odt / 2009 / AN9161298