Connection of detectors Labor Strauss
Chapter 2 • Conventional technology
21
2.4.1.3 Connection with Diode Base FC600/BRD
The detector base with integrated diode may only be used with a capacitive end-of-line element. At
the moment only the BC06 and the BC600 can fulfil this requirement. The installation of diode bases
with end-of-line resistors is not allowed. In the settings of the control panel, a capacitor must be para-
meterised as an end-of-line element.
2.4.1.4 Connection of detectors with Remote Indicator PA58-3 and Address Module NG58-1
Up to three remote indicators PA58-3 can be connected to the remote output of the detector. For this
purpose the „TAB“ of every remote indicator has to be broken out. When only one remote indicator is
connected to the detector, the „TAB“ must not be broken out.
Connection-LST.odt / 2009 / AN9161298
200/21