![LST BC016 Series Скачать руководство пользователя страница 195](http://html1.mh-extra.com/html/lst/bc016-series/bc016-series_user-manual_1944502195.webp)
Connection of detectors Labor Strauss
Chapter 4 • Analogue values - Condition of detectors/modules
195
4
Analogue values - Condition of detectors/modules
The condition of the detectors and modules Series FI700/FI750 is determined by the combination of
analogue values and the status message. The tables shown below only reflect the measurement value
and their meaning. As a consequence, the status message of the element also has to be taken into con-
sideration.
Example:
Control module with supervised output
Value: 15
According to the table on page 197 in Chapter 4.3.3: „Control module with supervision – output“ a
value of 15 can indicate either a
short circuit
or a
broken wire
at the output. The effective condition is
shown in the „Element Status“ information.
This status information can be indicated by pressing the „?“ button at the BC216/BC600 or via PAR-
SOFT by means of the table „Element Status“ where the readout of the analogue values takes place.
In contrast to the Fire Detection Control Panel Series BC600, the current degree of contamination of an
automatic detector with optical component is not indicated on the display of a Fire Detection Control
Panel Series BC216. By means of PARSOFT, the degree of contamination can be read out – this applies
to both control panel types. For further information in this regard, see from page 200 onwards in
Chapter 6: „Contamination detection and maintenance prognosis“.
4.1
Function of the LEDs
4.1.1
Automatic detectors
Please keep in mind that the condition of the LED in the alarm state is defined by the programming of
the control panel. The LED of an
automatic detector
has the following meaning:
Meaning
Yellow
Wrong type installed, double address, isolator active (BC600 only)
Red-blinking Alarm state
Red
LED-colour
Alarm state
4.1.2
Modules
Note that the LED condition also depends on the programming of the fire detection control panel. The
LED of a
module
has the following meaning:
Yellow
Activation of the input
Activation of the input
Actuation of the output
LED-colour Meaning
Wrong type installed, double address, input/output fault, fault of the
power supply
Red-blinking
Red
Green
4.1.3
Manual Call Points Series HFM/HME
Yellow
Wrong type installed, double address, isolator active (BC600 only)
Activation
Activation
Normal condition
LED-colour Meaning
Red-blinking
Red
Green
Connection-LST.odt / 2009 / AN9161298