Chapter 3 • ADM technology
Connection of detectors Labor Strauss
3.3.2.5 Setting the address
After power-on of the Programming Unit FI700/PU or FI750/PU, the text „Address“ is displayed on the
LCD. This indicates that the programming unit is in the addressing mode. In addition, the last selected
address is displayed in the second line.
Pressing the keys
or
will change the address. It can be set between 1 and 240. Keep in mind
that no double addresses on the loop are used.
By pressing the save button
, the displayed address will be saved into the device. A successful pro-
gramming will be indicated by the green flashing LED on the programmed device.
3.3.2.6 Reading the address
After power-on of the Programming Unit FI700/PU or FI750/PU, the text „Address“ is displayed on the
LCD.
By pressing the
button, the address of the connected device will be displayed in the second line of
the display.
3.3.2.7 Expert mode
If the
button is pressed for more than one second, the expert mode is started. Afterwards you must
select the device family (analogue/conventional). This is only possible since version 2.0.
In addition to the address, the following information can be read out:
Device type
Standard analogue value
Detection characteristics of a thermal detector
Contamination level of an optical or optical/thermal detector in percent
Firmware version
Production date
Test date
Operating Mode for setting the sound level of sounders.