Troubleshooting
524
LCD Display
Description
Over Load
Displayed when a motor is overloaded. Set PRT-17 to ‗1‘ to enable.
Set OUT-31–35 or OUT-36 to ‗5 (Over Load)‘ to receive the overload
warning output signals.
Under Load
Displayed when the motor is underloaded. Set PRT-25 is to ‗1‘. Set
the digital output terminal or relay (OUT-31–35 or OUT-36) to‘ 7
(Under Load)‘ to receive the underload warning output signals.
INV Over Load
Displayed when the overload time equivalent to 60% of the inverter
overheat protection (inverter IOLT) level, is accumulated. Set the
digital output terminals or relay (OUT-31–35 or OUT-36) to ‗6 (IOL)‘
to receive the inverter overload warning output signals.
Lost Command
Lost command warning alarm occurs even with PRT-12 set to ‗0‘.
The warning alarm occurs based on the condition set at PRT-13-15.
Set the digital output terminals or relay (OUT-31–35 or OUT-36) to
‗13 (Lost Command)‘ to receive the lost command warning output
signals.
Fan Warning
Displayed when an error is detected from the cooling fan while PRT-
79 is set to‘1‘. Set the digital output terminals or relay (OUT-31–35 or
OUT-36) to ‗8 (Fan Warning)‘ to receive the fan warning output
signals.
DB Warn %ED
Displayed when the DB resistor usage rate exceeds the set value.
Set the detection level at PRT-66.
Fire Mode
When there is a fire, Fire Mode forces the inverter to ignore certain
fault trips and continue to operate. Set the digital output terminals or
relay (OUT-31–35 or OUT-36) to ‗27 (Fire Mode)‘ to receive the fire
mode warning output signals.
Pipe Broken
Displayed when a pipe is broken during pump operation. Set the
digital output terminals or relay (OUT-31–35 or OUT-36) to ‗28 (Pipe
Broken)‘ to receive the pipe break warning output signals.
Lost Keypad
Displayed when a communication error occurs between the keypad
and the inverter, when PRT-11 (Lost KPD Mode) is set to any other
value than ‗0‘, and a run command is given from the keypad. Set the
digital output terminals or relay (OUT-31–35 or OUT-36) to ‗24 (Lost
KPD)‘ to receive the lost keypad warning output signals.
Level Detect
Displayed during a level detect state. Set PRT-70 to ‗1 (warning)‘ to
enable.
CAP. Warning
Displayed when capacitor life expectancy level goes below the level
set by the user. Set the digital output terminals or relay (OUT-31–35
or OUT-36) to ‗34 (CAPWarning)‘ to receive the capacitor life
warning output signals.
Fan ExChange
Displayed when the cooling fans need replacing. Set the digital
Содержание LSLV0055H100-4COFN
Страница 14: ......
Страница 18: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Страница 27: ...Preparing the Installation 13 ...
Страница 47: ...33 Installing the Inverter ...
Страница 48: ...Installing the Inverter 34 Input and Output Control Terminal Block Wiring Diagram ...
Страница 61: ...47 Installing the Inverter ...
Страница 71: ...Learning to Perform Basic Operations 57 ...
Страница 88: ...Learning to Perform Basic Operations 74 ...
Страница 103: ...89 Learning Basic Features Code Description V1 Quantizing ...
Страница 120: ...Learning Basic Features 106 Grou p Cod e Name LCD Display Parameter Setting Setting Range Unit Prev ...
Страница 129: ...115 Learning Basic Features ...
Страница 140: ...Learning Basic Features 126 ...
Страница 148: ...Learning Basic Features 134 ...
Страница 171: ...157 Learning Advanced Features Deceleration dwell operation ...
Страница 183: ...169 Learning Advanced Features ...
Страница 184: ...Learning Advanced Features 170 PID Command Block ...
Страница 185: ...171 Learning Advanced Features PID Feedback Block ...
Страница 186: ...Learning Advanced Features 172 PID Output Block ...
Страница 187: ...173 Learning Advanced Features PID Output Mode Block ...
Страница 197: ...183 Learning Advanced Features ...
Страница 201: ...187 Learning Advanced Features Code Description 100 EPID1 Control block ...
Страница 202: ...Learning Advanced Features 188 EPID2 Control block ...
Страница 237: ...223 Learning Advanced Features Time Period Schedule AP3 38 Except3 Day 01 01 ...
Страница 244: ...Learning Advanced Features 230 ...
Страница 259: ...245 Learning Advanced Features Code Description Code Description Volt ...
Страница 362: ...Learning Protection Features 348 ...
Страница 415: ...401 RS 485 Communication Features Item Standards Parity check None ...
Страница 524: ...Table of Functions 510 ...
Страница 533: ...Table of Functions 519 ...
Страница 547: ...533 Troubleshooting ...
Страница 564: ...Technical Specification 550 11 3 External Dimensions IP 20 Type 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Страница 585: ...Technical Specification 571 ...
Страница 594: ...580 ...
Страница 595: ...581 ...
Страница 596: ...582 ...