205
Learning Advanced Features
Note
Load tuning is not available while the inverter is operating.
•
If the frequencies for AP2-02 (Low Freq) and AP2-08 (High Freq) are set too close to each
other, the resulting load curve may not reflect the actual (ideal) load curve. Therefore, it is
recommended that you keep the AP2-02 and AP2-08 frequencies as close to the factory
defaults as possible.
•
If a secondary motor is in use, note that the existing load curve for the main motor will be
applied to the secondary motor unless a load tuning has been performed for the secondary
motor.
5.18 Level Detection
When the inverter is operating at or above the frequency set at PRT-74 (
LDT Level
)
, this
function is used to triggers a fault trip or sets a relay output if the source value is out of the
range of the user-defined values. If the reset restart feature is turned on, the inverter
continues to operate based on the run command after the LDT fault trip is released.
Group Code Name
LCD Display Parameter Setting
Setting Range Unit
PRT
70
Level detection
mode
LDT Sel
Warning
None/Warnin
g/Trip
71
Level detection
range
LDT Area
Sel
1 . Above Level
0–1
-
72
Level detection
source
LDT Source 0: Output Current
0–12
-
73
Level detection
delay time
LDT Dly
Time
2.0
0–9999
Sec
74
Level detection
reference value LDT Level
Source setting is
used
Source
setting is
used
-
75
Level detection
bandwidth
LDT Band
width
Source setting is
used
Source
setting is
used
-
Содержание LSLV0055H100-4COFN
Страница 14: ......
Страница 18: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Страница 27: ...Preparing the Installation 13 ...
Страница 47: ...33 Installing the Inverter ...
Страница 48: ...Installing the Inverter 34 Input and Output Control Terminal Block Wiring Diagram ...
Страница 61: ...47 Installing the Inverter ...
Страница 71: ...Learning to Perform Basic Operations 57 ...
Страница 88: ...Learning to Perform Basic Operations 74 ...
Страница 103: ...89 Learning Basic Features Code Description V1 Quantizing ...
Страница 120: ...Learning Basic Features 106 Grou p Cod e Name LCD Display Parameter Setting Setting Range Unit Prev ...
Страница 129: ...115 Learning Basic Features ...
Страница 140: ...Learning Basic Features 126 ...
Страница 148: ...Learning Basic Features 134 ...
Страница 171: ...157 Learning Advanced Features Deceleration dwell operation ...
Страница 183: ...169 Learning Advanced Features ...
Страница 184: ...Learning Advanced Features 170 PID Command Block ...
Страница 185: ...171 Learning Advanced Features PID Feedback Block ...
Страница 186: ...Learning Advanced Features 172 PID Output Block ...
Страница 187: ...173 Learning Advanced Features PID Output Mode Block ...
Страница 197: ...183 Learning Advanced Features ...
Страница 201: ...187 Learning Advanced Features Code Description 100 EPID1 Control block ...
Страница 202: ...Learning Advanced Features 188 EPID2 Control block ...
Страница 237: ...223 Learning Advanced Features Time Period Schedule AP3 38 Except3 Day 01 01 ...
Страница 244: ...Learning Advanced Features 230 ...
Страница 259: ...245 Learning Advanced Features Code Description Code Description Volt ...
Страница 362: ...Learning Protection Features 348 ...
Страница 415: ...401 RS 485 Communication Features Item Standards Parity check None ...
Страница 524: ...Table of Functions 510 ...
Страница 533: ...Table of Functions 519 ...
Страница 547: ...533 Troubleshooting ...
Страница 564: ...Technical Specification 550 11 3 External Dimensions IP 20 Type 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Страница 585: ...Technical Specification 571 ...
Страница 594: ...580 ...
Страница 595: ...581 ...
Страница 596: ...582 ...