229
Learning Advanced Features
5.23 Kinetic Energy Buffering
When the input power supply is disconnected, the inverter‘s DC link voltage decreases, and
a low voltage trip occurs blocking the output. A kinetic energy buffering operation uses
regenerative energy generated by the motor during the blackout to maintain the DC link
voltage. This extends the time for a low voltage trip to occur, after an instantaneous power
interruption.
Grou
p
Code Name
LCD Display
Parameter
Setting
Setting
range
Unit
CON
77
Kinetic energy buffering
selection
KEB Select
1
Yes
0–1
-
78
Kinetic energy buffering
start level
KEB Start
Lev
130
110–140
%
79
Kinetic energy buffering
stop level
KEB Stop Lev 135
125–145
%
80
Kinetic energy buffering
slip gain
KEB Slip
Gain
300
1–20000
-
81
Kinetic energy buffering
P-Gain
KEB P Gain
1000
1–20000
-
82
Kinetic energy buffering
I gain
KEB I Gain
500
1–20000
-
83
Kinetic energy buffering
acceleration time
KEB Acc
Time
10.0
0.0–600.0
Sec
command sources set in Freq Ref Src for DRV-07 (followed by Jog operation and multi-step
acc/dec).
If a fault trip occurs during a time event operation, the inverter stops the operation and
stays in a trip state. When this happens, there are two options to resume the stopped
operation:
•
Set PRT-08 (RST Restart) to ‗YES‘ to allow the inverter to automatically restart after
the trip condition is released.
•
Refresh the setting at AP3-70 (Time Event En). Set AP3-70 to ‗Yes‘ from ‗No‘. If one of
the input terminals (IN-65–71 Px Define) is assigned to it, turn the swtich off then turn it
back on to resume the time event operation.
Содержание LSLV0055H100-4COFN
Страница 14: ......
Страница 18: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Страница 27: ...Preparing the Installation 13 ...
Страница 47: ...33 Installing the Inverter ...
Страница 48: ...Installing the Inverter 34 Input and Output Control Terminal Block Wiring Diagram ...
Страница 61: ...47 Installing the Inverter ...
Страница 71: ...Learning to Perform Basic Operations 57 ...
Страница 88: ...Learning to Perform Basic Operations 74 ...
Страница 103: ...89 Learning Basic Features Code Description V1 Quantizing ...
Страница 120: ...Learning Basic Features 106 Grou p Cod e Name LCD Display Parameter Setting Setting Range Unit Prev ...
Страница 129: ...115 Learning Basic Features ...
Страница 140: ...Learning Basic Features 126 ...
Страница 148: ...Learning Basic Features 134 ...
Страница 171: ...157 Learning Advanced Features Deceleration dwell operation ...
Страница 183: ...169 Learning Advanced Features ...
Страница 184: ...Learning Advanced Features 170 PID Command Block ...
Страница 185: ...171 Learning Advanced Features PID Feedback Block ...
Страница 186: ...Learning Advanced Features 172 PID Output Block ...
Страница 187: ...173 Learning Advanced Features PID Output Mode Block ...
Страница 197: ...183 Learning Advanced Features ...
Страница 201: ...187 Learning Advanced Features Code Description 100 EPID1 Control block ...
Страница 202: ...Learning Advanced Features 188 EPID2 Control block ...
Страница 237: ...223 Learning Advanced Features Time Period Schedule AP3 38 Except3 Day 01 01 ...
Страница 244: ...Learning Advanced Features 230 ...
Страница 259: ...245 Learning Advanced Features Code Description Code Description Volt ...
Страница 362: ...Learning Protection Features 348 ...
Страница 415: ...401 RS 485 Communication Features Item Standards Parity check None ...
Страница 524: ...Table of Functions 510 ...
Страница 533: ...Table of Functions 519 ...
Страница 547: ...533 Troubleshooting ...
Страница 564: ...Technical Specification 550 11 3 External Dimensions IP 20 Type 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Страница 585: ...Technical Specification 571 ...
Страница 594: ...580 ...
Страница 595: ...581 ...
Страница 596: ...582 ...