Learning Protection Features
336
Under Load Trip and Warning Setting Details
Code
Description
PRT-23
UL Source
Select a source to detect the under load trip. An under load trip can be
detected using output current or output power.
PRT-24
UL Band
Make a standard value for the under load fault occurrence using
system load%-UL Band value set in each frequency of the load
characteristics curve made by the AP2-01 Load Tune.
PRT-25 UL Warn Sel
Select the under load warning options. Set the multi-function output
terminals (at OUT-31–35 and 36) to ‗7‘ (Under load). The warning
signals are output when under load conditions occur.
PRT-26 UL Warn
Time
A protect function operates when under load level condition explained
above maintains for the warning time set.
PRT-27 UL Trip Sel
Sets the inverter operation mode for situations when an under load
trip occurs. If set to ‗1 (Free-Run)‘, the output is blocked in an under
load fault trip event. If set to ‗2 (Dec)‘, the motor decelerates and stops
when an under load trip occurs.
PRT-28 UL Trip Time A protect function operates when under load level conditions
explained above maintain for the trip time set.
To operate under load trip properly, a load tuning (AP2-01 Load Tune) must be performed in
advance. If you cannot perform a load tuning, manually set the load fit frequencies (AP2-02
Load Fit Lfreq–AP2-10 Load Fit Hfreq). The Under Load protection does not operate while the
Energy Save function is in operation.
6.3.1 Fan Fault Detection
Group Code Name
LCD Display Parameter Setting Setting range Unit
PRT 79
Cooling fan fault
selection
Fan Trip
Mode
0
Trip
OUT 31–35 Multi-function
relay 1–5
Relay 1–5
8 Fan Warning
-
OUT 36
Multi-function
output 1
Q1 Define
Fan Fault Detection Setting Details
Содержание LSLV0055H100-4COFN
Страница 14: ......
Страница 18: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Страница 27: ...Preparing the Installation 13 ...
Страница 47: ...33 Installing the Inverter ...
Страница 48: ...Installing the Inverter 34 Input and Output Control Terminal Block Wiring Diagram ...
Страница 61: ...47 Installing the Inverter ...
Страница 71: ...Learning to Perform Basic Operations 57 ...
Страница 88: ...Learning to Perform Basic Operations 74 ...
Страница 103: ...89 Learning Basic Features Code Description V1 Quantizing ...
Страница 120: ...Learning Basic Features 106 Grou p Cod e Name LCD Display Parameter Setting Setting Range Unit Prev ...
Страница 129: ...115 Learning Basic Features ...
Страница 140: ...Learning Basic Features 126 ...
Страница 148: ...Learning Basic Features 134 ...
Страница 171: ...157 Learning Advanced Features Deceleration dwell operation ...
Страница 183: ...169 Learning Advanced Features ...
Страница 184: ...Learning Advanced Features 170 PID Command Block ...
Страница 185: ...171 Learning Advanced Features PID Feedback Block ...
Страница 186: ...Learning Advanced Features 172 PID Output Block ...
Страница 187: ...173 Learning Advanced Features PID Output Mode Block ...
Страница 197: ...183 Learning Advanced Features ...
Страница 201: ...187 Learning Advanced Features Code Description 100 EPID1 Control block ...
Страница 202: ...Learning Advanced Features 188 EPID2 Control block ...
Страница 237: ...223 Learning Advanced Features Time Period Schedule AP3 38 Except3 Day 01 01 ...
Страница 244: ...Learning Advanced Features 230 ...
Страница 259: ...245 Learning Advanced Features Code Description Code Description Volt ...
Страница 362: ...Learning Protection Features 348 ...
Страница 415: ...401 RS 485 Communication Features Item Standards Parity check None ...
Страница 524: ...Table of Functions 510 ...
Страница 533: ...Table of Functions 519 ...
Страница 547: ...533 Troubleshooting ...
Страница 564: ...Technical Specification 550 11 3 External Dimensions IP 20 Type 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Страница 585: ...Technical Specification 571 ...
Страница 594: ...580 ...
Страница 595: ...581 ...
Страница 596: ...582 ...