Chapter 3. General Specification
3-1
Chapter 3. General Specifications
General specifications of Rnet master, slave communication module are as follows.
[Table 3.1] General specification
No.
Item
Specification
Related
specification
1 Operating
temp. 0
℃∼
+55
℃
2 Storage
temp. -25
℃∼
+70
℃
3 Operating
moist. 5
∼
95%RH, non-condensing
4 Storage
moist. 5
∼
95%RH, non-condensing
For discontinuous vibration
Frequency Acceleration Amplitude
Number
10
≤
f< 57
㎐
-
0.075mm
57
≤
f
≤
150
㎐
9.8
㎨
(1G) -
For continuous vibration
Frequency Acceleration Amplitude
10
≤
f< 57
㎐
-
0.035mm
5 Vibration
57
≤
f
≤
150
㎐
4.9
㎨
(0.5G) -
Each 10 times in X,Y,Z
directions
IEC 61131-2
6 Impact
* Max. impact acceleration: 147
㎨
(15G)
* Authorized time: 11
㎳
* Pulse wave: Sign half-wave pulse (each 3 times in X,Y,Z directions)
IEC 61131-2
Square wave
Impulse noise
±1,500V
Test spec. reference
within LS Industrial
Systems
Static electric
discharging
Voltage : 4kV(Contact discharging)
IEC 61131-2,
IEC 61000-4-2
Radiation electric
field noise
27~500 MHz, 10V/m
IEC 61131-2,
IEC 61000-4-3
Segment Power module
Digital input/
output (24V or
more)
Digital input/output
(less than 24V)Analog
input/output
communication interface
7 Noise
Fast transient/burst
noise
Voltage
2kV 1kV
0.25kV
IEC 61131-2,
IEC 61000-4-4
8
Ambient conditions No corrosive gas and dust
9
Height
Up to 2000m
10 Pollution
level
]
2 or less
11
Cooling type
Natural air cooling
1) IEC (International Electrotechnical Commission)
: International non-governmental association, which establishes international standards in the field of electric and electronics.
2) Pollution level
: This is an indication showing pollution of surrounding environment, which determines insulation performance of device, and generally
the pollution level 2 means the conditions in which only non-conductive pollution occurs.
But, temporary conduction may occur according to condensing.
Note
3.1 General Specifications
Содержание G0L-GWRA
Страница 115: ...Appendix A 14 A3 5 G0L GWRA Applied type G0L GWRA ...