Appendix
A-1
Appendix
A1. Code Value and Description of STATUS of FB(GLOFA)/Command(MK)
A1.1 Error received from communication module
Error no.
GLOFA
(Decimal)
MK
(Hexade
cimal)
Description
0 H00
OK(Success : No error)
1 H01
Physical layer error of link side(Tx/Rx impossible)
– Cause of self error and other station's power off, other station No. writing error, and failure,
etc.
3 H03
There is no identifier of
function block
to be received in communication channel.
– Value not used in our company.
4 H04
Data type mismatch
5 H05
Reset received from other station
– Value not used in our company.
6 H06
Communication command of other station not ready
– Value not used in our company.
7 H07
Device state of remote station in wrong state
– Value not used in our company.
8 H08
Access denied to remote object
9 H09
Communication commands of other station unable to process due to receiver overrun
– Value not used in our company.
10 H0A
Time out for response waiting
– When response has not been received from other station within a given time.
11 H0B
Structure error
12 H0C
Abort(Local/Remote)
– Disconnected by serious error
13 H0D
Reject(Local/Remote)
– Type unfitted to MMS, error caused by noise.
15 H0F
High speed communication and connection service error
33 -
Cannot find variable identifier
– Not identified in the range of access variable
34 H22
Address error
– Error of structure and range specified in specifications of communication module
50 H23
Response error
– When response not received as required or other station's CPU error
113 H71
Object access unsupported
– Out of VMD specific and symbolic address or exceeded max. value of data length
187 HBB
Received via another error code than specified code(Other company's communication code
value)
– Receiving another error code value than specified.
Содержание G0L-GWRA