Chapter 9. Trouble Shooting
9-10
9.2.8 Error code E03-02: High speed link not run
Is link-enable set to ‘On’?
High speed link
is not operating.
Yes
No
Is network
configuration perfect?
Correct the setting of station
number by referring to function
description of
high speed link
in
6.2.
Are
network type, slot,
and self station number of the
link setting identical with
appropriate
slot?
No
Is setting
method of station number
for each registration item
correct?
Correct the link setting
according to network type,
station number, and slot
number of appropriate slot.
Download parameter again.
Check and correct it according
to the flow of error code E01-
01.
Yes
End
Yes
Yes
Set appropriate link-enable to
‘On’.
No
Is TR area
relevant among registration
items?
Adjust the range of Tx/Rx area
by referring to CPU type and
base parameter.
Is there any
error of other station
among registration
items?
Set link enable setting to ‘On’.
Yes
No
Remove the error of other
station.
Yes
No
No