Appendix
A-2
A1.2 STATUS values indicated in CPU
1) Error processed within communication commands
Error no.
GLOFA
(Decimal)
MK
(Hexadec
imal)
Description
16
H10
When position of computer communication module is wrongly specified.
17
H11
Initialization error of communication module mounted in SLOT_NO
18
H12
Input parameter setting error
19
H13
Variable length error
20
H14
Wrong response receiving from other station
21
H15
When no response received from computer communication module
(Out of waiting time - Time out)
2) STATUS error related to remote(RSM) function block
Error no.
GLOFA
(Decimal)
MK
(Hexadeci
mal)
Description
128 H80
RSM power error
129 H81
BASE(Rack) No. error
130 H82
Slot No. error
131 H83
Module information error
132 H84
Data range error(Invalid range)
133 H85
Data type mismatch
136 H88
Access failure(BUS access error)
137 H89
Another error than specified code
Содержание G0L-GWRA
Страница 115: ...Appendix A 14 A3 5 G0L GWRA Applied type G0L GWRA ...