Chapter 6. Communication Function
6-13
Link parameter basic screen
◎
Link 1: as a high-speed link type, K1000S can have max. 4, K300S/K200S can have max.2,
K80S can have only one communication module. High-speed link no. doesn’t have relation with
slot no., One high-speed link can be set per one communication module. The following table
indicates communication type and max. no. for equipment according to CPU.
Module equipment relation per CPU type
Classification
Comm. Module
Max. equipment no.
Reference
K1000S G3L-RUEA
4
K300S(less than v2.2)
G4L-RUEA
2
K300S(more than v2.2)
G4L-RUEA
4
K200S G6L-RUEA 2
K80S G7L-RUEA 1
Available to mix each
communication module
◎
Link: whether executing the communication module link
◎
Self station no.: self station no. should be ‘0’.
◎
Slot: slot no. where communication module is equipped. Rage is from ‘0’ to ‘7’.
◎
Registration no.: indicates the registered no. of each parameter. Range is 0~63. This doesn’t
have relation with TX/RX sequence. It is available to register max. 32 per TX and RX.