![LS Industrial Systems G0L-GWRA Скачать руководство пользователя страница 87](http://html.mh-extra.com/html/ls-industrial-systems/g0l-gwra/g0l-gwra_user-manual_1943825087.webp)
Chapter 9. Trouble Shooting
9-1
Chapter 9. Trouble Shooting
This chapter explains all of error contents which may occurs during system management, cause detection,
and how to take action. If error occurred in communication module, error contents are displayed through
LED of communication module. At this time, user can read error indication(Ex. RMM_06) according to
appropriate LED status from Appendix, and perform troubleshooting according to error code(Ex. E00-01)
from error indication in this chapter.
9.1 Abnormal Operations
[Table 9.1(A)] H/W related error of communication module
Error code
Error indication
(See LED contents of Appendix)
Error contents
E00-01
RMM_06 ~ RMM_10
RMM_24 ~ RMM_27
RSM_05 ~ RSM_10
RSM_32
MCM_06 ~ MCM_09
Hardware self diagnosis error among LED
indication of each module.
E00-02
RMM_11 ~ RMM_13
MCM_11
Interface diagnosis error with PLC among LED
indication of each module.
E00-03
FOU_41, FOU_42, FOU_43, FOU_44
FOU_51, FOU_52, FOU_61, FOU_62
Power and hardware error of FOU group
occurred.
E00-04
RSM_08 ~ RSM_10
Initialization of I/O and special module in slave
group.
[Table 9.1(B)] Abnormal communication status of communication module
Error code
Error indication
Error contents
E01-01
RMM_16 ~ RMM_21
RSM_13 ~ RSM_16
RSM_31, RSM_33
Communication error in master and slave group
of Rnet (Communication is not made well).
E01-03
FOU_41, FOU_42, FOU_43
FOU_51, FOU_61
Communication error in FOU group of Rnet
(Communication is not made well).
[Table 9.1(C)] Abnormal interface operation of PLC of communication
Error code
Error indication
Error contents
E02-01
RMM_22, RMM_23
MCM_11
Interface with PLC in master and
communication module group is not made well.
E02-02
RSM_08 ~ RSM_10
Interface error with I/O module in slave group
of Fnet.
Содержание G0L-GWRA