ERROR CODE TABLES
3OHDVHUHIHUWRWKH6DIHW\3UHFDXWLRQVRQSDJHVIRUPRUHGHWDLOWRSUHYHQWLQMXU\RUGHDWKUHJDUGLQJWKHRSHUDWLRQDQGVHUYLFH
troubleshooting of the Chiller product.
WARNING
Error
Code
Description
Reason
Chiller Status
Error Resolution
CHxx034
Surge in high pressure
Surge in high pressure side.
Stop applicable
cycle
Automatically return to normal
condition
CHxx035
Surge in low pressure
Drop in low pressure side.
Stop applicable
cycle
Automatically return to normal
condition
CHxx036
Low compression rate error
Low compression rate error.
Stop applicable
cycle
Automatically return to normal
condition
CHxx040
Inverter compressor CT sensor
error
Inverter compressor CT sensor is
disconnected, shorted, or opened.
Stop applicable
cycle
Automatically return to normal
condition
CHxx041
Inverter compressor discharge
temperature sensor error
Inverter compressor discharge
temperature sensor is
disconnected, shorted, or opened.
Stop applicable
cycle
Automatically return to normal
condition
CHxx042
Low pressure sensor error
Low pressure sensor is
disconnected, shorted, or opened.
Stop applicable
cycle
Automatically return to normal
condition
CHxx043
High pressure sensor error
High pressure sensor is
disconnected, shorted, or opened.
Stop applicable
cycle
Automatically return to normal
condition
CHxx045
Heat exchanger temperature
sensor error
Heat exchanger temperature sensor is
disconnected, shorted, or opened.
Stop applicable
cycle
Automatically return to normal
condition
CHxx046
Suction temperature sensor
error
Suction temperature sensor is
disconnected, shorted, or opened.
Stop applicable
cycle
Automatically return to normal
condition
CHxx050
Chiller 3 phase power missing
phase
Chiller 3 phase power missing phase
Stop applicable
cycle
Automatically return to normal
condition
CHxx052
Communication error with
inverter controller
Communication error with inverter
controller
Stop applicable
cycle
Automatically return to normal
condition
CHxx053 Communication failure between
indoor and chiller units.
Communication failure between indoor
and chiller unit.
Stop applicable
cycle
Automatically return to normal
condition
CHxx054
Reversed phase on chiller
unit’s 3 phased power source;
Reversed connection on RST.
Reversed phase on chiller unit’s 3 phased
power source; Reversed connection on
RST.
Stop applicable
cycle
Automatically return to normal
condition
CHxx057
Communication error with
inverter controller
Communication error with inverter
controller
Stop applicable
cycle
Automatically return to normal
condition
CHxx059
Installation failure of series
model outdoor unit
Installation failure of series model outdoor
unit
Stop applicable
cycle
Automatically return to normal
condition
CHxx060
Inverter PCB EEPROM error
Inverter PCB EEPROM error
Stop applicable
cycle
Automatically return to normal
condition
CHxx062
Surge in inverter board IPM
temperature
Surge in inverter board IPM temperature
Correspond cycle
stop
Automatic return to a normal
condition
CHxx065
Inverter IPM temperature
sensor error
Inverter IPM temperature sensor is
disconnected, shorted, or opened.
Stop applicable
cycle
Automatically return to normal
condition
CHxx067
Fan lock
Fan locked
Stop applicable
cycle
Automatically return to normal
condition
CHxx075
Fan CT sensor error
Fan CT sensor is disconnected, shorted,
or opened.
Stop applicable
cycle
Automatically return to normal
condition
CHxx077
Fan over-voltage error
Fan over-voltage
Stop applicable
cycle
Automatically return to normal
condition
Table 44: Error Code Table, continued.