View Chiller Information - Load Water Temperature Screen
Chiller information includes load water temperature, pump / flow amount status, and, system information.
Icon
Description
E.W.T Displays the common load entering water temperature value.
L.W.T
Displays the common load leaving water temperature value.
HMI SCREENS
View Chiller Information - Pump / Flow Amount Status
Screen
Figure 30: Load Water Temperature Screen.
Table 8: Load Water Temperature Screen Table.
Icon
Description
Pump Output
If it is in operation, it always maintains an ON state.
When the chiller operation stops, the freeze and burst prevention mode is applied, and operates as follows:
According to the outdoor air temperature condition, the load water pump repeats operation ON and OFF.
2XWGRRU$LU7HPSHUDWXUH)ĺ$OZD\V³21´
)2XWGRRU$LU7HPSHUDWXUH)ĺWZRPLQXWHRSHUDWLRQDQGHLJKWHHQPLQXWHVWRS
2XWGRRU$LU7HPSHUDWXUH)ĺ2SHUDWLRQ³2))´
The freeze and burst prevention mode is possible when the pump is connected.
To interface with the pump, the pump output connect is to be installed. To verify that the pump operates, the pump interlock
connector is to be installed. (For installation,see the connection diagram.)
Pump Interlock
Receives the status of the load water pump output through the external signal contact point of the pump.
(When the chiller is in operation, the pump output maintains an “ON” state, otherwise, an alarm will occur.)
Flow Switch
Displays the current load water’s flow amount switch status value.
(When the chiller is in operation, the pump output maintains an “ON” state, otherwise, an alarm will occur.)
Capacity
Displays the capacity of the device.
Figure 31: Pump / Flow Amount Status Screen.
Table 9: Pump / Flow Amount Status Screen Table.