77
T
roubleshooting / Error Codes
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
3OHDVHUHIHUWRWKH6DIHW\3UHFDXWLRQVRQSDJHVIRUPRUHGHWDLOWRSUHYHQWLQMXU\RUGHDWKUHJDUGLQJWKHRSHUDWLRQDQGVHUYLFH
troubleshooting of the Chiller product.
WARNING
Symptom
Cause
Solution
Reverberating sound.
Rubber on the motor mount is defective.
Replace motor mount.
Pipe vibration heard near compressor.
Replace the anti-vibration material on piping.
High frequency wave
sound from front of
chiller.
Fan defect in the control box.
Clean the area around the fan.
Constantly searching for
cold water.
Insufficient cold water.
Check the water system (Ensure rated flow).
- Is the water system valve closed?
- Is the pressure difference between inlet and outlet of the
water system appropriate?
- Is the air of water system cold?
- Is the cooling load within appropriate range?
Evaporation pressure is
high.
Temporary rise in water temperature due to abnormal
load increase.
This is a normal condition, but verify if the pressure falls within
the operating range.
Table 42: Troubleshooting General Errors, continued.
TROUBLESHOOTING GENERAL ERRORS