65
Pre-Commissioning
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Register Address
Description
10001
Reserve
10002
0 : Load Water Flow Switch Off
1 : Load Water Flow Switch On
10003
Reserve
10004
0 : Load Water Pump Output Off
1 : Load Water Pump Output On
10005
Reserve
10006
0 : Load Water Pump Interlock Off
1 : Load Water Pump Interlock On
10007 ~ 10104
Reserve
10105
0 : 4 Way Valve 1 Off of Cycle 1
1 : 4 Way Valve 1 On of Cycle 1
10106
0 : 4 Way Valve 2 Off of Cycle 1
1 : 4 Way Valve 2 On of Cycle 1
10107
0 : Hot gas1 Off of Cycle 1
1 : Hot gas1 On of Cycle 1
10108
0 : Hot gas2 Off of Cycle 1
1 : Hot gas2 On of Cycle 1
10109
0 : Sump Heater 1 Off of Cycle 1
1 : Sump Heater 1 On of Cycle 1
10110
0 : Sump Heater 2 Off of Cycle 1
1 : Sump Heater 2 On of Cycle 1
10111~10118
Reserve
10119
0 : Inverter Compressor 1 Off of Cycle 1
1 : Inverter Compressor 1 On of Cycle 1
10120
0 : Inverter Compressor 2 Off of Cycle 1
1 : Inverter Compressor 2 On of Cycle 1
10121~10208
Reserve
10209
0 : 4 Way Valve 1 Off of Cycle 2
1 : 4 Way Valve 1 On of Cycle 2
10210
0 : 4 Way Valve 2 Off of Cycle 2
1 : 4 Way Valve 2 On of Cycle 2
Modbus Protocol Registers
Coil Register
Table 31: Coil Register.
Register Address
Description
1
0: Product Stop, 1: Operation Start
Table 32: Discrete Registers.
Discrete Registers
MODBUS PROTOCOL REGISTERS