69
Pre-Commissioning
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Table 36: Input Registers, continued.
Register Address
Description
30301, 30302
Load Water Output Temperature of Cycle 3
30303, 30304
Load Water Input Temperature of Cycle 3
30305~30308
Reserve
30309
Condensation Temperature (Left) of Cycle 3
30310
Condensation Temperature (Right) of Cycle 3
30311
Evaporation Temperature (Left) of Cycle 3
30312
Evaporation Temperature (Right) of Cycle 3
30313
Inverter Compressor 1 Frequency of Cycle 3
30314
Inverter Compressor 2 Frequency of Cycle 3
30315
High Pressure (Left) of Cycle 3
30316
High Pressure (Right) of Cycle 3
30317
Low Pressure (Left) of Cycle 3
30318
Low Pressure (Right) of Cycle 3
30319
Operation Current (Left) of Cycle 3
30320
Operation Current (Right) of Cycle 3
30321
Main EEV’s Status Value of Cycle 3 (Left)
30322
Main EEV’s Status Value of Cycle 3 (Right)
30323~30324
Reserve
30325
Discharge Temperature of Inverter Compressor 1 of Cycle 3
30326
Discharge Temperature of Inverter Compressor 2 of Cycle 3
30327
Intake Temperature of Inverter Compressor 1 of Cycle 3
30328
Intake Temperature of Inverter Compressor 2 of Cycle 3
30329
Liquid Pipe Temperature (Left) of Cycle 3
30330
Liquid Pipe Temperature (Right) of Cycle 3
30331
Hex Temperature (Left) of Cycle 3
30332
Hex Temperature (Right) of Cycle 3
30333~30344
Reserve
30345
Accumulated Operation Time of Inverter Compressor 1 of Cycle 3 (Upper Level)
30346
Accumulated Operation Time of Inverter Compressor 1 of Cycle 3 (Lower Level)
30347
Accumulated Operation Time of Inverter Compressor 2 of Cycle 3 (Upper Level)
30348
Accumulated Operation Time of Inverter Compressor 2 of Cycle 3 (Lower Level)
30349~39997
Reserve
39998
Product Group Info.
39999
Product Type Info.
Table 37: Holding Registers.
Register Address
Description
40001
Reserve
40002
Operation Mode Setting (0 : Cooling, 4 : Heating)
40003
Cooling Target Temperature Setting (41°F ~ 68°F)
40004
Heating Target Temperature Setting (104°F ~ 134.6°F)
40005
Control Mode Setting (On-site/Remote/Scheduled)
40006
Remote Mode Setting (Contact / Modbus)
40007
Cooling Type Setting (0 : Normal)
40008
Max. Operating Frequency Setting: (0 : 120, 1 : 130, 2 : 110, 3 : 100, 4 : 90, 5 : 80, 6 : 70)
40009~40022
Reserve
Holding Registers
MODBUS PROTOCOL REGISTERS