ERROR CODE TABLES
3OHDVHUHIHUWRWKH6DIHW\3UHFDXWLRQVRQSDJHVIRUPRUHGHWDLOWRSUHYHQWLQMXU\RUGHDWKUHJDUGLQJWKHRSHUDWLRQDQGVHUYLFH
troubleshooting of the Chiller product.
WARNING
Error Code
Description
Reason
Chiller Status
Error Resolution
CHxx077
Fan over-voltage error
Fan over-voltage
Stop applicable
cycle
Automatically return to normal
condition
CHxx079
Fan start failure error
Fan start failure
Stop applicable
cycle
Automatically return to normal
condition
CHxx086
Main PCB EEPROM error
Main PCB EEPROM access error
Stop applicable
cycle
Automatically return to normal
condition
CHxx087
Fan PCB EEPROM error
Fan PCB EEPROM access error
Stop applicable
cycle
Automatically return to normal
condition
CHxx090
Individual Inlet water
temperature sensor error
Individual Inlet water temperature sensor is
disconnected, shorted, or opened.
Stop applicable
cycle
Automatically return to normal
condition
CHxx091
Individual Outlet water
temperature sensor error
Individual Outlet water temperature sensor is
disconnected, shorted, or opened.
Stop applicable
cycle
Automatically return to normal
condition
CHxx104
Communication Error between
units.
Communication error between units.
Stop applicable
cycle
Automatically return to normal
condition
CHxx105
Fan board communication error
Fan board communication error.
Stop applicable
cycle
Automatically return to normal
condition
CHxx106
Fan PCB IPM fault
Fan PCB IPM fault.
Stop applicable
cycle
Automatically return to normal
condition
CHxx107
Fan DC link low voltage error
Fan DC link low voltage.
Stop applicable
cycle
Automatically return to normal
condition
CHxx113
Liquid pipe temperature sensor
error
Liquid temperature sensor is disconnected,
shorted, or opened.
Stop applicable
cycle
Automatically return to normal
condition
CHxx114
Sub cooling suction
temperature sensor error
Sub cooling suction temperature sensor is
disconnected, shorted, or opened.
Stop applicable
cycle
Automatically return to normal
condition
CHxx115
Sub cooling outlet pipe
temperature sensor error
Sub cooling outlet pipe temperature sensor is
disconnected, shorted, or opened.
Correspond cycle
stop
Automatic return to a normal
condition
CHxx145
Main Board - External Board
communication Error
Main Board - External Board communication
Error
Stop applicable
cycle
Automatically return to normal
condition
CHxx150
Liquid Compression Prevention
Error
Liquid Compression Prevention Error
Stop applicable
cycle
Automatically return to normal
condition
CHxx151 Reversing valve switching failed
Mode switching failed
Stop applicable
cycle
Automatically return to normal
condition
CHxx180
Shell and tube type heat
exchanger frozen.
Cooling: Individual output water temperature
is maintained at 37.4°F or lower for at least
10 seconds.
Heating: Individual output water temperature
is maintained at 140°F or higher for at least
10 seconds.
Common in heating and cooling: The
difference in input and output water
temperature is maintained at 44.6°F or
higher for at least 30 seconds.
and / or
If the low pressure is maintained at less than
65.7 psi after the compressor started.
Stop applicable
cycle
Automatically return to normal
condition
CHxx193 Surge in fan board heat emitting
plate temperature
Surge in fan board heat sink temperature
Stop applicable
cycle
Automatically return to normal
condition
CHxx194
Fan board heat emitting plate
temperature sensor error
Fan board heat emitting plate temperature
sensor is short/open
Stop applicable
cycle
Automatically return to normal
condition
Table 45: Error Code Table, continued.