Table 43: Error Code Table.
Error
Code
Description
Reason
Chiller Status
Error Resolution
CHxx001
Outdoor temperature sensor
error.
Outdoor temperature sensor is
disconnected, shorted, or opened.
Stop product.
Automatically returns to normal
condition.
CHxx003
HMI communication error.
When communication between HMI and
chiller controller is disconnected for more
than 180 seconds.
Stop product.
Automatically return to normal
condition.
CHxx005
Cycle control box
communication error.
When communication between chiller
controller and cycle control box is
disconnected for more than 30 seconds.
Stop product
Automatically return to normal
condition.
CHxx009
Remote communication error.
When the Modbus communication with
the external device is not established for
more than 180 seconds after the initial
communication with the remote Modbus
condition is established.
Stop product
Automatically return to normal
condition.
CHxx011
Load water pump interlock
error.
When the load water pump is turned off
for 3 seconds when starting or during
the operation for more than 3 times within
1 hour. When turned off more than 9
seconds within 1 hour.
Stop product
Press the HMI Reset button.
CHxx013
Load water flow switch error.
When the load water flow switch is turned
off for 3 seconds when starting or
during the operation for more than 3 times
within 1 hour. When turned off more than 9
seconds within 1 hour.
Stop product
Press the HMI Reset button.
CHxx015
Remote alarm.
When the contact point signal of hardware
wiring is short when entering the remote
control mode.
Stop product
Automatically return to normal
condition.
CHxx021
Inverter compressor IPM fault.
Inverter compressor drive IPM defect/
inverter compressor defect
Stop applicable
cycle
Automatically return to normal
condition.
CHxx022 Inverter compressor input over-
current.
Inverter compressor input over-current.
Stop applicable
cycle
Automatically return to normal
condition.
CHxx023
Inverter compressor DC link
low pressure.
DC voltage charge defect.
Stop applicable
cycle
Automatically return to normal
condition.
CHxx024
Cycle high pressure switch
operation.
High pressure switch operates due to
abnormal high pressure.
Stop applicable
cycle
Automatically return to normal
condition.
CHxx025
High/Low voltage of input
voltage.
Over/Under permitted voltage of input
voltage, N.
Stop applicable
cycle
Automatically return to normal
condition.
CHxx026
Inverter compressor start
failure error.
Initial start failure from compressor defect.
Stop applicable
cycle
Automatically return to normal
condition.
CHxx028
Inverter DC link high voltage
error.
Defect from DC voltage and over-charge.
Stop applicable
cycle
Automatically return to normal
condition.
CHxx029
Inverter compressor over-
current.
Exceed limit.
Stop applicable
cycle
Automatically return to normal
condition.
CHxx032
Surge in inverter #1,#2
compressor discharge
temperature.
Stop applicable
cycle
Automatically return to normal
condition