Air-Cooled Cooling Only Inverter Scroll Chiller Installation and Owners Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
ELECTRICAL DATA
Tons
Model No.
Voltage Frequency
(Hz)
Voltage Tolerance
(Min. ~ Max.)
MCA
MFA
Compressor
Chiller Fan
Motor
Input Power
MSC
RLA
kW
FLA
kW
20
ACAH020HETB
460
60
414 ~ 506
31
40
9.7
24.9
1.8
5
21.5
Table 2: Electrical Data for Single 460V Cooling Only Chiller.
Voltage Range: Power supplied to the chiller must fall within the voltage minimum to
maximum range listed in the table above. The chiller will not operate normally if the power
supply voltage falls below or above the tolerance range.
Maximum allowable voltage variance permitted between phases is 2%.
MCA: Minimum Circuit Ampacity (A) (Criteria used to select the wiring standard).
MFA: Maximum Fuse Amps (A) (Criteria used to select circuit breaker and ground error
circuit breaker [electricity leakage circuit breaker]).
MSC: Maximum Start Current (A)
RLA: Rated Load Amps (A) (Current required when operating under the following
conditions
—
Cooling: Outdoor Air Temperature: 8
°
1F DB / 66
°
F WB; Water Inlet / Outlet
Temperature: 54
°
F / 44
°
F).
FLA: Full Load Amps (A).