Table 34: Input Registers.
Register Address
Description
30001
Chiller Controller Version
30002
Entire Operation Current
30003
External Air Temperature
30004
Common Load Water Output Temperature (Average Value of Individual Load Water Outputs)
30005
Common Load Water Input Temperature (Average Value of Individual Load Water Inputs)
30006~30007
Reserve
30008
Information of Refrigerator Failure (1~5)
30009
Cycle Failure Information (0 : Common System Error, 1~10 : Error of Corresponding Cycle)
30010
Failure Code
30011
Start Waiting Time
30013
Product’s Accumulated Operation Time Upper Level
30014
Product’s Accumulated Operation Time Lower Level
30015~30100
Reserve
30101, 30102
Load Water Output Temperature of Cycle 1
30103, 30104
Load Water Input Temperature of Cycle 1
30105~30108
Reserve
30109
Condensation Temperature (Left) of Cycle 1
30110
Condensation Temperature (Right) of Cycle 1
30111
Evaporation Temperature (Left) of Cycle 1
30112
Evaporation Temperature (Right) of Cycle 1
30113
Inverter Compressor 1 Frequency of Cycle 1
30114
Inverter Compressor 2 Frequency of Cycle 1
30115
High Pressure (Left) of Cycle 1
30116
High Pressure (Right) of Cycle 1
30117
Low Pressure (Left) of Cycle 1
30118
Low Pressure (Right) of Cycle 1
30119
Operation Current (Left) of Cycle 1
30120
Operation Current (Right) of Cycle 1
30121
Main EEV’s Status Value of Cycle 1 (Left)
30122
Main EEV’s Status Value of Cycle 1 (Right)
30123~30124
Reserve
30125
Discharge Temperature of Inverter Compressor 1 of Cycle 1
30126
Discharge Temperature of Inverter Compressor 2 of Cycle 1
30127
Intake Temperature of Inverter Compressor 1 of Cycle 1
30128
Intake Temperature of Inverter Compressor 2 of Cycle 1
MODBUS PROTOCOL REGISTERS
Input Registers