Air-Cooled Cooling Only Inverter Scroll Chiller Installation and Owners Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Operation
Range
Cold Water Inlet
Temperature
46.4°F or above
Cold Water Outlet
Temperature
39.2°F to 68°F
Outdoor
Temperature
5°F to 118.4°F
5()5,*(5$173,3,1*$1'6(1625',$*5$0
OPERATION RANGE AND LIMIT
Figure 6: Single Chiller Refrigerant Piping and Sensor Location Diagram (ACAH020HETB).
M
S
Cooling
Refrigerant
Fan Motor
Pressure Sensor
Pressure Switch
Solenoid Valve
Check Valve
Strainer
Electronic Expansion
Valve
Expansion Valve
Flow Switch
Temperature Sensor
Compressor
2
Air cooled
condenser
Air cooled
condenser
Oil
separator
Oil
Separator
Sub-cooler
Water-out
Water-in
Accumulator
Accumulator
Compressor
1
Sub-cooler
Operation Range and Limit
The table and the diagram shows the operation
range of the product.
'RQRWRSHUDWHWKHH[FHHGWKHRSHUDWLRQUDQJHRI
the chiller.
Refrigerant Piping and Sensor Diagram
Figure 5: Cooling Mode Operation Range Diagram.
-4°F
14° 32°F 50°F 68°F 86°F 104°F 122°F
Outdoor Temperature
50°F
59°F
68°F
77°F
41°F
Water Temperature
118.4°F
46.4°F
Outlet Water Temperature
Inlet Water Temperature
•
,IRXWVLGHWHPSHUDWXUHLVEHORZ)GHSHQGLQJRQLQOHWWHPSHUDWXUHWKHFKLOOHUZLOOQRWRSHUDWHQRUPDOO\RUZLOOUXQIRUDQH[WHQGHGWLPHLI
in cooling mode. If this is the case, increase the inlet temperature by circulating the load water, and then operate in cooling.
• Add antifreeze if the chiller is to operate in ambient air temperatures below 41°F (the water in the pipes could freeze).
Table 3: Operation Range and Limit Table.