Air-Cooled Cooling Only Inverter Scroll Chiller Installation and Owners Manual
TROUBLESHOOTING GENERAL ERRORS
3OHDVHUHIHUWRWKH6DIHW\3UHFDXWLRQVRQSDJHVIRUPRUHGHWDLOWRSUHYHQWLQMXU\RUGHDWKUHJDUGLQJWKHRSHUDWLRQDQGVHUYLFH
troubleshooting of the Chiller product.
WARNING
Troubleshooting General Errors
If the safety devices stopped chiller operation, identify and resolve the problem(s) before restart.
• If the chiller is not operating, check the power, refrigerant, configuration, and error settings.
• To troubleshoot the power supply / wiring, check the voltage connected to the chiller terminal block in the control panel. If there is no power,
check if the circuit breaker has tripped.
• If the power is properly connected, check the chiller refrigerant cycle pressure to verify if it is within the normal range.
• If the chiller refrigerant cycle pressure exceeds the normal range, check for leaks within the piping system.
• Before restarting the chiller, return it the default setting.
• Check the error codes; error codes can be view using the HMI device.
• If there is /are (an) error code(s) the alarm is turned on, see the Error Code tables to troubleshoot specific errors.
Symptom
Cause
Solution
Chiller does not start.
Check the power.
Check over-current protection device.
Check if fuse is disconnected or shorted out.
Turn power on.
Incorrect or inaccurate chiller configuration.
Check configuration.
Check if wiring is incorrect.
Error appears.
Check the error condition.
Check for the error code tables to review solutions and resolve
the issue.
Follow direction.
Check the HMI input channel to review the error input.
Entering delay time.
Verify if the compressor is in start delay time.
Evaporation pressure is
low and the chiller is
constantly stopping.
Insufficient refrigerant.
Check for leaks and recharge refrigerant.
Insufficient water.
Check water system (ensure rated flow.).
- Is the water system valve closed?
- Is the pressure difference between inlet and outlet of the
water system appropriate?
- Is the air from water system cold?
Condensation pressure
is high and the chiller is
constantly stopping.
Outside temperature is high.
Check if the outside temperature is within the operation
condition range.
Foreign particles accumulated on the condenser.
Clean condenser.
Fan is defective.
Replace fan.
Chiller is vibrating.
Bolt connecting the fan motor is loose.
Check assembly and tighten bolt.
Motor mount is loose.
Check assembly and tighten bolt.
Fan is not balanced.
Check fan rotation range; replace fan.
Compressor assembly bolt is loose.
Tighten assembly bolt / nut.
Frame assembly bolt is loose.
Check assembly and tighten bolt
Motor bearing is burned.
Check for abnormal noise in motor (noise in multiple RPM)
and replace motor.
Table 41: Troubleshooting General Errors.