Step 9.
If you are replacing a power supply to the server, attach the redundant power information label that
comes with this option on the server cover near the power supplies.
Power supplies
Figure 124. Redundant power information label
Replacing a hot-swap dc power supply
Use this information to replace a hot-swap dc power supply.
The following notes describe the type of power supply that the server supports and other information that
you must consider when you install a power supply:
• Before you install an additional power supply or replace a power supply with one of a different wattage,
you may use the Power Configurator utility to determine current system power consumption. For
more information and to download the utility, go to http://www-03.ibm.com/ systems/bladecenter/
resources/powerconfig.html.
• The server comes with one hot-swap 12-volt output power supply that connects to power supply bay 1.
The input voltage is -48 V dc or -60 V dc auto-sensing.
• Before you install a dc power supply in the server, you must remove all ac power supplies. Do not use
both ac and dc power supplies in the same server. Install up to two dc power supplies or up to two ac
power supplies, but not a combination.
• Power supply 1 is the default/primary power supply. If power supply 1 fails, you must replace the power
supply with the same wattage immediately.
• You can order an optional power supply for redundancy.
• These power supplies are designed for parallel operation. In the event of a power-supply failure, the
redundant power supply continues to power the system. The server supports a maximum of two
power supplies.
• It is the customer's responsibility to supply the necessary power cable.
To reduce the risk of electric
shock or energy hazards:
–
Use a proper circuit breaker.
–
Use 4 mm
2
(10 AWG) at 90° C copper wire.
–
Torque the wiring-terminal screws to 0.50 ~ 0.60 newton-meters (4.43 ~ 5.31 inch-pounds).
For more information, see Statement 34 below.
• If the power source requires ring terminals, you must use a crimping tool to install the ring terminals to
the power cord wires. The ring terminals must be UL approved and must accommodate the wire that is
described in the above-mentioned note.
204
Lenovo System x3550 M5 Installation and Service Guide
Содержание System x3550 M5
Страница 1: ...Lenovo System x3550 M5 Installation and Service Guide Machine Type 8869 ...
Страница 6: ...iv Lenovo System x3550 M5 Installation and Service Guide ...
Страница 66: ...52 Lenovo System x3550 M5 Installation and Service Guide ...
Страница 298: ...284 Lenovo System x3550 M5 Installation and Service Guide ...
Страница 1120: ...1106 Lenovo System x3550 M5 Installation and Service Guide ...
Страница 1124: ...1110 Lenovo System x3550 M5 Installation and Service Guide ...
Страница 1132: ...Taiwan BSMI RoHS declaration 1118 Lenovo System x3550 M5 Installation and Service Guide ...
Страница 1134: ...1120 Lenovo System x3550 M5 Installation and Service Guide ...
Страница 1142: ...1128 Lenovo System x3550 M5 Installation and Service Guide ...
Страница 1143: ......
Страница 1144: ......