Fig. 12: Connection diagram with vent valve
The external application must be connected according to the sketch (Fig. 12)
so that gas/vapor bubbles can be removed from the system and undisturbed
operation is possible. The outflow of the pump must be connected to the
lower connection of the application. The return line to the pump connector
must be connected to the top connection of the application. The application
is thus flowed through from bottom to top.
Hose nozzle:
n
Push the hose onto the hose nozzle. Secure the hoses against slipping
using hose clips or similar.
Ball bush and hose nozzle:
n
The sealing surfaces of the cone and ball bush/hose nozzle may not be
damaged (falling onto hard ground or similar).
n
Carefully remove dirt from the sealing surfaces (cone and ball bush /
hose nozzle) before assembly.
n
Place the ball bush/hose nozzle vertically on the cone (support the hose
when tightening).
n
The ball bush / hose nozzle may not rotate when tightening the union
nut (if necessary apply some grease or oil between the ball bush / hose
nozzle and union nut).
n
Tighten the union nut only moderately with the open-end wrench and
hold it against the connecting sleeve with a second open-end wrench.
Mounting instructions for connecting an
application
V4
Integral process thermostats with flow control unit
32 / 171
Содержание IN 550 XT
Страница 61: ...5 3 2 Menu structure Fig 26 Menu Part 1 V4 Integral process thermostats with flow control unit 61 171...
Страница 157: ...14 Declaration of Conformity and certificates V4 Integral process thermostats with flow control unit 157 171...
Страница 158: ...Fig 85 Declaration of Conformity V4 Integral process thermostats with flow control unit 158 171...
Страница 159: ...Fig 86 Declaration of Conformity V4 Integral process thermostats with flow control unit 159 171...
Страница 161: ...V4 Integral process thermostats with flow control unit 161 171...
Страница 162: ...V4 Integral process thermostats with flow control unit 162 171...
Страница 171: ...Y Year of construction 23 V4 Integral process thermostats with flow control unit 171 171...