O2-Control
6
O
2
-Control
6.1
What happens if a fault occurs in the O
2
regulation
In the event of malfunction, the display shows a warning and the O
2
control is deactivated.
The specified base value "without control” or the one for "air deficiency” is set. The display
shows the running text "O
2
regulation perturbed”.
The burner doesn’t shut down.
Set the selector switch to "Status" to call up the corresponding error code.
6.1.1
How to switch the Display
WARNING!
You can set the O
2
trim only, if you have completed the programming of the compound.
6.2
Air Deficiency Pertubation
If the O
2
actual value is significantly smaller than the O
2
setpoint value (below the second
monitoring band) and corrective actions by the ETAMATIC cannot clear this error, the regula-
tion will be deactivated and the base value for air deficiency errors will be output. If desired,
the ETAMATIC triggers an air deficiency burner shut-down. Therefor set parameter 897 to 1.
The error code is H360, "Error shut-down by O
2
regulator”.
6.3
Resetting O
2
-errors
Each new burner start-up resets O
2
errors automatically. This is permissible, because a 100%
O
2
measurement test is performed at each start-up.
Manual resetting of O
2
errors is possible at any time, as follows:
Press key 11 ENTER
The display shows a plain text message about the cause of
the error.
Press key 15 to change the display from status of the compound to O
2
value (if active)
and to flame intensity (if active). If neither O
2
trim, nor integrated flame scanner is
active, key 15 has no function.
Press key RESET
ETAMATIC in O
2
trim mode?
If not, switch over to O
2
trim mode
Press key 15 M once
Press key ENTER and call up the cause of error (mandatory!)
Press key 7
Содержание ETAMATIC
Страница 1: ...Manual ETAMATIC ETAMATIC S CE 0085 AU 0207 Sensors and Systems for Combustion Engineering...
Страница 2: ......
Страница 7: ...6 Table of Contents 9 27 Dimensions and weight 128 9 28 Declaration of Conformity 131...
Страница 65: ...64 8 Control Mode 8 2 1 Leakage test flow chart Fig 8 4 Flow chart leakage test...
Страница 69: ...68 8 Control Mode Switching in standby via LSB module Fig 8 7 Switching in Standby mode via LSB module...
Страница 90: ...89 9 Appendix 9 8 Process Sequence Charts Fig 9 3 Process sequence chart gas with pilot burner...
Страница 91: ...90 9 Appendix Fig 9 4 Process sequence chart oil with pilot burner...
Страница 92: ...91 9 Appendix Fig 9 5 Process sequence chart gas without pilot burner...
Страница 93: ...92 9 Appendix Fig 9 6 Process sequence chart oil without pilot burner...
Страница 98: ...97 9 Appendix 9 9 Connection Diagrams Fig 9 7 ETAMATIC wiring diagram with ignition flame monitoring...
Страница 99: ...98 9 Appendix Fig 9 8 ETAMATIC S wiring diagram with ignition flame monitoring...
Страница 104: ...103 9 Appendix Fig 9 16 LSB connection ETAMATIC LT1 other LAMTEC devices...
Страница 134: ...133 9 Appendix...
Страница 135: ......