![Lamtec ETAMATIC Скачать руководство пользователя страница 112](http://html2.mh-extra.com/html/lamtec/etamatic/etamatic_manual_3440151112.webp)
111
9
Appendix
Technical data of the Namur input: U
O
= 8,2V; Ik = 8,2mA, +/- 5%
–
make threshold: max 2.1 mA (typical 1.8 mA)
–
break threshold: max. 1.2 mA (type 1.4 mA)
–
linearity error: < 0,1% v. E.
–
temperature drift: < 75 ppm/K (type. 60ppm/K)
Direct connection of Speed sensor (actual version)
This option allows you to connect a inductive sensor for revolution pickup directly. It could be
a NAMUR type or a three wired type. The selection of the type and the range is only factory
setting. Sensor NAMUR type is connected to terminal 42 and 43, three wired type to terminal
42,43 and 44 or 22.
Speed nominal range (164...819 digit):
•
I 30 ... 300 pulses / min.
•
II 600 ... 7200 pulses / min.
•
III 300 ... 3600 pulses / min. (standard)
•
IV 60... 600 pulses / min
lower limit (152 digit) / upper limit (991 digit)
•
I 20 ... 350 pulses / min.
•
II 355 ... 8430 pulses / min.
•
III 175 ... 4220 pulses / min. (standard)
•
IV 40... 700 pulses / min
If the set pulse range is exceeded the value remains at the upper end of the range (higher
pulse numbers are ignored). Below the measuring range the signal goes to approx. 0 - 7 digit.
The standard setting is range III (i.e. on motors with 3000 rpm at 50 Hz, 1 pulse per revolution)
WARNING!
Make sure that the selected measuring range is not exceeded, otherwise speed changes in
excess of this will no longer be detected.
Owing to the large number of usable transducers LAMTEC has only one two wire element and
one three wire element in it’s product range. It is selected in that way, that it covers a number
of measuring tasks. Other transducers only on enquiry or direct from the company Turck.
Technical Data
linearity error
< 0,1% v. E.
temperature drift
< 75 ppm/K (typical 60 ppm/K)
Namur input
U
O
= 8,2 V; Ik = 8,2 mA, +/- 5%
make threshold:
max. 1,98 mA (typical 1,8 mA), +/- 5%
break threshold:
max. 1,62 mA (typical 1,4 mA), +/- 5%
Switch input
make threshold:
6,2V
break threshold:
4,5V
Measuring method
period duration measurement over 5 periods
Input pulse width:
>200 µs
Temperature range:
0…60 °C / 32°F...140°F
Usable Namur trans-
mitters
all Turck sensors, which contain Y0 or Y1 in their type designa-
tion.
Содержание ETAMATIC
Страница 1: ...Manual ETAMATIC ETAMATIC S CE 0085 AU 0207 Sensors and Systems for Combustion Engineering...
Страница 2: ......
Страница 7: ...6 Table of Contents 9 27 Dimensions and weight 128 9 28 Declaration of Conformity 131...
Страница 65: ...64 8 Control Mode 8 2 1 Leakage test flow chart Fig 8 4 Flow chart leakage test...
Страница 69: ...68 8 Control Mode Switching in standby via LSB module Fig 8 7 Switching in Standby mode via LSB module...
Страница 90: ...89 9 Appendix 9 8 Process Sequence Charts Fig 9 3 Process sequence chart gas with pilot burner...
Страница 91: ...90 9 Appendix Fig 9 4 Process sequence chart oil with pilot burner...
Страница 92: ...91 9 Appendix Fig 9 5 Process sequence chart gas without pilot burner...
Страница 93: ...92 9 Appendix Fig 9 6 Process sequence chart oil without pilot burner...
Страница 98: ...97 9 Appendix 9 9 Connection Diagrams Fig 9 7 ETAMATIC wiring diagram with ignition flame monitoring...
Страница 99: ...98 9 Appendix Fig 9 8 ETAMATIC S wiring diagram with ignition flame monitoring...
Страница 104: ...103 9 Appendix Fig 9 16 LSB connection ETAMATIC LT1 other LAMTEC devices...
Страница 134: ...133 9 Appendix...