![Lamtec ETAMATIC Скачать руководство пользователя страница 30](http://html2.mh-extra.com/html/lamtec/etamatic/etamatic_manual_3440151030.webp)
29
5
Commissioning
Control Range
Select parameter no. 802 and 803
No
FMS
ETA
Short Text
Description
Min
Max
Default
798
0
0
Soll2min
Controller set-point 2 minimum
0
999
70
Firing-rate controller set point 2 minimum (set point 2)
in ° C or bar (xx.x)
Enter the minimum value for the second controller set
point (active if input "set point switching" = 1) (control by
atmospheric condition). Enter the setpoint in this param-
eter, if the firing-rate controller is configured to constant
controller,
see P 796
refer to figure "Control by Atmospheric Conditions
/ Setpoint Switching of the Firing-rate Controller"
No
FMS
ETA
Short Text
Description
Min
Max
Default
802
0
0
EinschPt
Burner start point
999
999
1
Enter the switching point of the firing-rate controller as
the difference to the set point.
[Switching point] = [setpoint] - [parameter content]
e. g. : burner should switch on at 110.
setpoint = 120, parameter content = 10,
110 = 120 - 10
If the burner shall start above the setpoint,
you may enter negative values as well.
Therefore the following values correspond:
-1 = 65535 and -999 = 94537
Parameter content = 65536 - difference
i. e.: burner shall switch on at 125.
set point = 120, parameter content = 65536 - 5 = 65531
switching point value= 120 - (-5) = 125
803
0
0
Regelb.O
upper Control range
0
999
10
(difference to the set point 1/2) in ° C or bar (xx.x)
Enter the upper control range limit.
The entered value corresponds to the difference
between the actual setpoint and the upper limit of the
control range.
Depending on the content of Parameter 809, the con-
tent of this parameter is interpreted as ° C (directly with-
out decimal point) as bar (resolution 0.1 bar, i.e. range
from 0.1 to 99.9 bar) or in digit.
see figure "Control range of the Firing-rate Controller"
Содержание ETAMATIC
Страница 1: ...Manual ETAMATIC ETAMATIC S CE 0085 AU 0207 Sensors and Systems for Combustion Engineering...
Страница 2: ......
Страница 7: ...6 Table of Contents 9 27 Dimensions and weight 128 9 28 Declaration of Conformity 131...
Страница 65: ...64 8 Control Mode 8 2 1 Leakage test flow chart Fig 8 4 Flow chart leakage test...
Страница 69: ...68 8 Control Mode Switching in standby via LSB module Fig 8 7 Switching in Standby mode via LSB module...
Страница 90: ...89 9 Appendix 9 8 Process Sequence Charts Fig 9 3 Process sequence chart gas with pilot burner...
Страница 91: ...90 9 Appendix Fig 9 4 Process sequence chart oil with pilot burner...
Страница 92: ...91 9 Appendix Fig 9 5 Process sequence chart gas without pilot burner...
Страница 93: ...92 9 Appendix Fig 9 6 Process sequence chart oil without pilot burner...
Страница 98: ...97 9 Appendix 9 9 Connection Diagrams Fig 9 7 ETAMATIC wiring diagram with ignition flame monitoring...
Страница 99: ...98 9 Appendix Fig 9 8 ETAMATIC S wiring diagram with ignition flame monitoring...
Страница 104: ...103 9 Appendix Fig 9 16 LSB connection ETAMATIC LT1 other LAMTEC devices...
Страница 134: ...133 9 Appendix...
Страница 135: ......