82
9
Appendix
in the case of fault 904, 911 915, in particular, check the corresponding reference, In the un-
loaded condition (terminal open) it is 2.4 V. With potentiometer connected somewhat lower,
depending on the resistance of the potentiometer. Though the reference voltage has to apply
stably, if you adjust the potentiometer across the whole range.
Enter the reference value with a new connected potentiometer.
A23
Fault 116, 400
The monitoring processor and the main processor may not have precisely the same load rat-
ing, so that one has the old point overwritten, whilst the other has a new point added.
This is possible particularly where the load ratings of the individual points lie close together.
Re-enter curve
A24
Storing 120
Different operating modes on main and monitoring processors. The digital input signals are
detected at slightly different times on main processor and monitoring processor.
A signal change occurs only for such a short instant that the main processor detects it but the
monitoring processor does not.
Check signal sequence
A 25
At oil flames: decrease flame scanner intensity (see chapter 9.2.1 Integral flame monitoring
(option))
A26
The ETAMATIC uses a test-current for testing the fail safe outputs. This current must flow
through connected loads (valves etc).
Check, that the current can flow. If not use a RC combination from the output terminal to neu-
tral.
Check fuses.
reference voltage
external contact at connector loop is possibly inverted,
Enter password and press 14
Press 13
new reference value is stored
Содержание ETAMATIC
Страница 1: ...Manual ETAMATIC ETAMATIC S CE 0085 AU 0207 Sensors and Systems for Combustion Engineering...
Страница 2: ......
Страница 7: ...6 Table of Contents 9 27 Dimensions and weight 128 9 28 Declaration of Conformity 131...
Страница 65: ...64 8 Control Mode 8 2 1 Leakage test flow chart Fig 8 4 Flow chart leakage test...
Страница 69: ...68 8 Control Mode Switching in standby via LSB module Fig 8 7 Switching in Standby mode via LSB module...
Страница 90: ...89 9 Appendix 9 8 Process Sequence Charts Fig 9 3 Process sequence chart gas with pilot burner...
Страница 91: ...90 9 Appendix Fig 9 4 Process sequence chart oil with pilot burner...
Страница 92: ...91 9 Appendix Fig 9 5 Process sequence chart gas without pilot burner...
Страница 93: ...92 9 Appendix Fig 9 6 Process sequence chart oil without pilot burner...
Страница 98: ...97 9 Appendix 9 9 Connection Diagrams Fig 9 7 ETAMATIC wiring diagram with ignition flame monitoring...
Страница 99: ...98 9 Appendix Fig 9 8 ETAMATIC S wiring diagram with ignition flame monitoring...
Страница 104: ...103 9 Appendix Fig 9 16 LSB connection ETAMATIC LT1 other LAMTEC devices...
Страница 134: ...133 9 Appendix...
Страница 135: ......